Optimization of Battery Storage Capacity with Min-Max Power Dispatching Method for Wind Farms

  • Published : 2013.07.02

Abstract

It is a crucial requirement to utilize an economical battery capacity for the wind energy conversion system. In this paper, the optimal BESS capacity is determined for the wind farm whose dispatched power is assigned by the min-max dispatching method. Based on a lifetime cost function that indicates the BESS cost spent to dispatch 1kWh wind energy into grid, the battery capacity can be optimized so as to obtain the minimum system operation cost. Moreover, the battery state of charge (SOC) is also managed to be in a safe operating range to ensure the system undamaged. In order to clarify the proposed optimizing method, a 3MW permanent magnet synchronous generator (PMSG) wind turbine model and real wind speed data measured each minute are investigated.

Keywords