Abstract
According to the statistical report from National Emergency Management Agency (NEMA) in Korea, the accident rate of closed switchboards in power systems occupies over 40%. In this paper, an integrated sensor module for monitoring the condition of closed switchboards is described. The sensor module monitors electro-magnetic (EM) wave, ultra-violet (UV) ray, heat and smoke generated by electrical discharges or insulation breakdown. The effective detection ranges were decided from experiment results; 100 kHz~10 MHz for EM wave, 220 nm~395 nm for UV ray and 0~
Keywords