Riverbank Filtration Well Development for a Heat Source/Sink of Ground Water Heat Pumps

시설원예 냉난방을 위한 온도차에너지 열원용 충적대수층 강변여과수 개발

  • Published : 2010.06.17

Abstract

Riverbank filtration wells have been developed to supply a heat source/sink of water in the alluvium aquifer to ground water heat pumps for cooling and heating of a green house. In order to look for an appropriate site to carry out the research, two sites of Jinju and Gumi areas were investigated. In the results of the electrical resistivity surveys, Jinju and Gumi areas have the alluvium aquifer in the depth of 6~17 m and 10~20 m under the ground respectively. Two boreholes have been drilled in each site of both areas. The averaged water level at Jinju site is about 3 m under the ground, and 3.5 m and 6.5 m of sandy gravel aquifer layers are existed in each site. While Gumi site has 10 m water level and 2.5 m and 4.6 m of sandy gravel aquifer. Therefore, it is expected that $1,000m^3$/day of water could be withdrawn at Jinju site rather than Gumi site.

Keywords