Cooling and Heating Performance Under the Actual Operating Condition of a Ground Source Heat Pump System in a School Building

학교 건물에 설치된 지열원 열펌프 시스템의 실사용을 통한 냉난방성능 연구

  • Kim, Eui-Young (School of Mechanical Engineering, Pusan National University) ;
  • Jeong, Young-Man (School of Mechanical Engineering, Pusan National University) ;
  • Song, Jae-Do (School of Mechanical Engineering, Pusan National University) ;
  • Lee, Jae-Keun (School of Mechanical Engineering, Pusan National University) ;
  • Kim, In-Kyu (Digital Appliance Laboratory, LG Electronics) ;
  • Lee, Dong-Hyuk (Digital Appliance Laboratory, LG Electronics)
  • Published : 2009.06.25

Abstract

This paper presents the performance of a water-to-refrigerant type ground source heat pump (GSHP) system installed in a school building in Korea. For analyzing the performance of the GSHP system, we monitored various operating conditions, including the outdoor temperature, the ground temperature, and the input power of the GSHP system. The average cooling coefficient of performance (COP) of the heat pump was found to be 8.5 at 60% partial load condition, while the overall system COP was found to be 5.9. The average heating COP of the heat pump was found to be 6.5 at 45% partial load condition, while the overall system COP was found to be 5.0.