Proceedings of the SAREK Conference (대한설비공학회:학술대회논문집)
- 2009.06a
- /
- Pages.52-57
- /
- 2009
Verification experiment of a ground source multi-heat pump at heating season
지열원 멀티 히트펌프의 동절기 난방성능에 관한 실증 연구
- Choi, Jong-Min (Department of Mechanical Engineering, Hanbat National University) ;
- Lim, Hyo-Jae (Department of Mechanical Engineering, Hoseo University) ;
- Kang, Shin-Hyung (Department of Mechanical Engineering, Konyang University) ;
- Choi, Jae-Ho (Graduate School of Mechanical Engineering, Hoseo University) ;
- Moon, Je-Myung (Air-conditiongin R&D Group, Samsung Electronics Co. Ltd.) ;
- Kwon, Young-Seok (Air-conditiongin R&D Group, Samsung Electronics Co. Ltd.) ;
- Kwon, Hyung-Jin (Air-conditiongin R&D Group, Samsung Electronics Co. Ltd.) ;
- Kim, Rock-Hee (Air-conditiongin R&D Group, Samsung Electronics Co. Ltd.)
- 최종민 (국립한밭대학교 기계공학과) ;
- 임효재 (호서대학교 기계공학과) ;
- 강신형 (건양대학교 기계공학과) ;
- 최재호 (호서대학교 기계공학과 대학원) ;
- 문제명 (삼성전자 생활가전 사업부) ;
- 권영석 (삼성전자 생활가전 사업부) ;
- 권형진 (삼성전자 생활가전 사업부) ;
- 김록희 (삼성전자 생활가전 사업부)
- Published : 2009.06.25
Abstract
This paper describes the multi-heat pumps applied in an ground source heat pump system for an actual building. The performance of a ground source multi-heat pump installed in the field was investigated at heating season. The average COP of the systems with single U-tube and double tube type GLHXs were 4.8 and 5.0, respectively. It is needed to investigate the long term performance of double tube type GLHX, because the reduction of inlet temperature of OD HX for this GLHX was larger than it for U-tube GLHX.