에너지절약형 주택에서의 단열차양 적용과 제어방법에 따른 냉난방부하 분석

An Analysis of Heating and Cooling Loads by Insulated Shades and Control Method in an Energy Saving Apartment

  • Kwon, Kyung-Woo (Technology Research Institute, Daelim Industrial Company Limited) ;
  • Won, Jong-Seo (Technology Research Institute, Daelim Industrial Company Limited)
  • 발행 : 2009.06.25

초록

Energy loss from windows accounts for large scores of heating and cooling loads also in energy saving apartments that is reduced over 30% of total energy consumption. Movable reflective insulations, insulation shutters, blinds, insulated shades are used to reduce energy loads from windows. In this study, energy saving performance of insulated shades was simulated by control methods. According to installation of insulated shades, heating loads were decreased about $10.5{\sim}11.3%$, and cooling loads are decreased about $11.0{\sim}15.5%$ on an energy saving apartment. The heating peak load was reduced about 9.5% by insulated shades, but the cooling peak load is hardly ever decreased. Because in the condition of cooling peak load, latent cooling loads accounts for large score of cooling loads. Difference of the energy loads by a schedule control method and an outdoor detection control was no more than 5% for a base model. In the case of insulated shades with automatic control system, simple time schedule control system would be more efficient than outdoor detection control system that should use several sensors.