Electrical Power and Energy Reference Measurement System with Asynchronous Sampling

비동기 샘플링에 의한 전력과 에너지 측정 기준시스템

  • Published : 2009.07.14

Abstract

A digital sampling algorithm that uses a two high resolution integrating Voltmeters which are synchronized by Phase Lock Loop (PLL) time clock for accurately measuring the parameters, active and reactive power, for sinusoidal power measurements is presented. The PLL technique provides high precision measurements, root mean square (rms), phase and complex voltage ratio, of the AC signal. The system has been designed to be used at the Korean Research Institute of Standards and Science (KRISS) as a reference power standard for electrical power calibrations. The test results have shown that the accuracy of the measurements is better than $10 {\mu}W/VA$ and the level of uncertainty is valid for the power factor range zero to 1 for both lead and lag conditions. The system is fully automated and allows power measurements and calibration of high precision wattmeters and power calibrators at the main power frequencies 50 and 60 Hz.

Keywords