A Study on the Characteristics of HTS Cable System Operation and Cooling Load in a Load Unbalance
불평형 부하에서의 초전도케이블 운전 및 냉각부하 특성에 관한 연구
- Sohn, S.H. (KEPRI) ;
- Lim, J.H. (KEPRI) ;
- Yang, H.S. (KBSI) ;
- Choi, H.O. (KERI) ;
- Ma, Y.H. (CNU) ;
- Kim, D.L. (KBSI) ;
- Ryoo, H.S. (KERI) ;
- Ryu, K.W. (CNU) ;
- Hwang, S.D. (KEPRI)
- 손송호 (한전 전력연구원) ;
- 임지현 (한전 전력연구원) ;
- 양형석 (한국기초과학지원연구원) ;
- 최하옥 (한국전기연구원) ;
- 마용호 (전남대학교) ;
- 김동락 (한국기초과학지원연구원) ;
- 류희석 (한국전기연구원) ;
- 류경우 (전남대학교) ;
- 황시돌 (한전 전력연구원)
- Published : 2009.07.14
Abstract
Demonstrations to deploy high temperature superconducting (HTS) cable to the real gird are actively carried out throughout the world. Power utilities have an interest in the inherent advantage of the HTS cable system, and achieve the expected results from the series of verification test. To embody the reliability in the phenomenon occurred commonly in three-phase system, we simulate the load unbalance. A 22.9 kV large scale HTS cable system with the specification of 100 m-long, 50 MVA capacity has been tested with up to 30% unbalance rate. To evaluate the effect of AC loss increase due to the unbalanced load, the cooling loads are measured by the calorimetry method. In this paper, the correlation between AC loss and load unbalance is described and investigated precisely.