A Study on the Variation of the Thermal Load for a House According to the Earth Sheltering Method

복토 주택의 복토 방법에 따른 열부하의 변화에 관한 연구

  • 이재혁 (인하대학교 대학원 건축공학과) ;
  • 최원기 (한화건설 기술연구소) ;
  • 서승직 (인하대학교 건축학부) ;
  • 조동우 (한국건설기술연구원 건축도시환경연구실)
  • Published : 2008.04.12

Abstract

We cannot imagine any more the environment and energy problems are separated from our lives. The various attempts to solve these problems are made all over the world. In this study it was performed to analyze a different heating and cooling load depending on the earth-sheltering method and kind of soils by using TRNSYS 16 as the first step to establish the design guidelines for earth-sheltered architecture, one of the eco-friendly and low energy consuming building types. After performing this simulation, we found the result like this. It is the most lowest load in case of all of walls and roof being earth-sheltered. But considering of the load reduction rate, the effect of earth-sheltering the exterior vertical wall is more efficient for load reduction than the one of earth-sheltering a roof. And we got a lower thermal load in case of a lower heat conductivity of soil. Afterwards we will conduct a further study for boundary condition at earth-sheltered surface and the simulation analysis about the sensitivity variables. The final goal of this study is preparing the design guidelines for earth-sheltered architecture. so we will contribute to building energy saving.