Abstract
This study is to measure the change of the $CO_2$ and floating dust concentration depending on the volume of the ventilation and the state of on/off the ventilation for the estimation of the air pollution in classroom. The results could be summarized as follows: the test cell was the two full scaled model and the one is set up with ventilation system another was not. the volume of classroom is 170.1m3 and the number of persons are 35. 1)when the ventilation system was not installed, The experimental results of the $CO_2$ concentration showed the average of 2,150ppm and the maximum of 2,740ppm in the classroom. This was the higher than 1,000ppm, the standard value of ASHRAE and the enforcement regulations of School Sanitation Code in Ministry of Education & Human Resources Development, 1000ppm. The $CO_2$ concentration was relatively increasing during school hours. 3)In case of the volume of ventilation of $800m^3$/h, the $CO_2$ concentration of classroom showed the average of 962 ppm and the maximum of 1,380 ppm. This was higher than 1,000ppm, the standard of ASHRAE and the enforcement regulations of School Sanitation Code in Ministry of Education & Human Resources Development. 4)The floating dust(PM10) was the maximum of 0.52 mg/$m^3$, the minimum of 0.25 mg/$m^3$, and the average of 0.32 mg/$m^3$ in case of the ventilation system off. Those were higher than the standard value 0.15 mg/$m^3$. In case of the ventilation system on, the floating dust(PM10) was the maximum of 0.174 mg/$m^3$ , the minimum of 0.048 mg/$m^3$, and the average of 0.078 mg/$m^3$. These were the lower than 0.15 mg/$m^3$, the standard of the enforcement regulations of School Sanitation Code in Ministry of Education & Human Resources Development. 5)The concentrations of $CO_2$ and PM10 were largely depending on the number of students and the ventilation system, The installation of the ventilation system is necessary for the amenity environment and the management of the indoor air quality.