Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference (한국전기전자재료학회:학술대회논문집)
- 2008.06a
- /
- Pages.491-492
- /
- 2008
Series-Gap Characteristics of Polymeric Arrester for Transmission Line
송전선로용 폴리머 피뢰기의 직렬공극 특성
- Cho, Han-Goo (KERI) ;
- Yoo, Dae-Hoon (KERI) ;
- Lee, Young-Sun ;
- Kim, Jong-Che
- Published : 2008.06.19
Abstract
This paper describes the series-gap characteristics of transmission line arrester with switching and lightning impulse flashover test. The transmission line arrester exhibited external gap because it is must not flashover with switching impulse on the other hand it is must flashover with lightning impulse. In accordance, minimum and maximum length of series-gap was determinated with these tests. As gap length is increased flashover voltage was increased in the range of 315.4 kV~496.3 kV and negative polarity exhibited a high voltage. As a result, It was thought tat the series-gap length of transmission line arrester exhibited in the range of 580 mm~1100 mm.