Circuital Characteristics of Ideal Three-phase Transformer Connections

이상적인 3상 변압기 결선의 회로 특성

  • Published : 2008.04.25

Abstract

Mathematical singularities of circuit equations with three-phase ideal transformer connections are studied. Three-wired wye-wye connections, delta-delta connections, and primary four-wired wye-delta connections are singular. The matrices of their circuit equations have zeros in their eigenvalues. Three-wired wye-delta connections, wye-wye-delta connections, and primary four-wired wye-wye connections are not singular. The physical meaning of their singularities is that they are sensitive and prone to be ill-conditioned. Equivalent shunt admittances representing ion losses and magnetizing inductances make the singular matrices non-singular in wye-connected circuits. And, equivalent series impedances representing copper losses and leakage inductances make the singular matrices non-singular in delta-connected circuits. The tableau analysis is used for the study.

Keywords