Fire Suppression Experiment for Road Tunnel Low Pressure Water Spray Systems

도로터널 저압 물분무설비 화재진압 실험

  • 최병일 (한국기계연구원 에너지기계연구본부) ;
  • 한용식 (한국기계연구원 에너지기계연구본부) ;
  • 김명배 (한국기계연구원 에너지기계연구본부) ;
  • 소수현 (한국소방검정공사 기술연구소)
  • Published : 2008.04.24

Abstract

The real scale fire suppression test inside a road tunnel were carried out for water spray systems. The dimension of the tunnel is 7.5m in height and 11.6m in width. 3 different water spray nozzle systems with low operating pressure less than 3.5 bar were used in the experiment. Two types of fires were tested. One is a $1.4m^2$ heptane pool fire and the other is a 2000CC passenger car fire. From the experiment, the spray densities of tested systems were about $6.0\;l/min/m^2$ which is currunt domestic guideline. Although all the systems cannot extinguish the tested fires, it was found that they can reduce the tunnel temperature and have a capability to control and suppress the tested fire.

Keywords