Example study of the insulation characteristic change according to the dryness condition in high voltage motor stator winding

고압전동기 고정자권선의 건조상태에 따른 절연특성 변화사례 고찰

  • Published : 2008.07.16

Abstract

This paper is purpose to understand the insulation properties of the high voltage motor stator winding according to the different dryness conditions. we carried out the three times insulation diagnosis test for the same motor stator winding. the first test object is the contaminated winding, second is the washed-out, and natural dried during the 24 hours, and the last is the heating dried in 110$^{\circ}C$ during the 48 hours. the insulation diagnosis tests are consist of the megger, the polarization index, the AC current test, the dissipation factor test and the partial discharge test, we analyzed and made a comparison of the three cases test result.

Keywords