가스인젝션을 적용한 이산화탄소 열펌프의 난방성능에 관한 실험적 연구

Experimental Study on the Heating Performance of a $CO_2$ Heat Pump with Gas Injeciton

  • 백창현 (고려대학교 기계공학과 대학원) ;
  • 이응찬 (고려대학교 기계공학과 대학원) ;
  • 강훈 (고려대학교 기계공학과) ;
  • 김용찬 (고려대학교 기계공학과) ;
  • 조성욱 (삼성전자 DA연구소)
  • 발행 : 2007.11.30

초록

In this study, experimental study on the heating performance of a $CO_2$ heat pump with gas injection was performed varying gas injection ratio and outdoor temperature to improve the heating performance of $CO_2$ heat pump. The twin rotary compressor having volume ratio of 0.7 was adopted in the $CO_2$ heat pump. From the test results, the heating capacity and COP were increased and the compressor discharge temperature was decreased with the increase of injection ratio. At the outdoor temperature of $-8^{\circ}C$, the heating capacity and COP with the injection were increased by 45% and 24%, respectively, compared with non-injection condition.

키워드