An Experimental Study on Thermal Stratification of Pressurized Plenum Underfloor Air Distribution System during Cooling

가압식 바닥급기 시스템의 여름철 성층화 경향에 관한 실험적 연구

  • 김동희 (한국건설기술연구원 건축도시환경 연구실) ;
  • 유기형 (한국건설기술연구원 건축도시환경 연구실) ;
  • 조동우 (한국건설기술연구원 건축도시환경 연구실) ;
  • 서정석 ((주)한일엠이씨) ;
  • 한성필 (한국건설기술연구원 건축도시환경 연구실)
  • Published : 2007.11.30

Abstract

The underfloor air distribution system has been attracting to architects and building owners as one of valuable system for the renovated and newly office building. In this paper, we discussed the thermal stratification profile of pressurized plenum underfloor air distribution(UFAD) according to indoor setting temperature, diffuser number, diffuser type. For this, the space of office building(H corp.) is selected for measuring the air volume of underfloor diffuser and vertical temperature profile. As a result, the thermal stratification profile is influenced by the number and type of the underfloor diffuser and thermal storage character of the underfloor. Whereas indoor setting temperature have a lower significant impact on thermal stratification.

Keywords