부분방전 신호의 누적검출과 뉴럴-퍼지 알고리즘을 이용한 컴퓨터 진단에 관한 연구

A study on the computer diagnosis that apply Neural-Fuzzy algorithm accumulation detection of Partial Discharge signal

  • 발행 : 2007.07.18

초록

In this paper, we have studied for analysis of the partial discharge(PD) signal in power transmission line. The PD signal has estimated as detected signal accumulation of a PRPDA method by using Labview, and analyzed with neural-fuzzy algorithm. With practical PD logic implementation of theoretical detected system and hardware implementation, the device for Hipotronics Company's 22.9kV or 154kV setup have generated and then have applied with 18kV,20kV with 1:1 time probe. It's also used the LDPE 0.27mmt (scratch error 0.05mmt) to sample for making PD. Our new class of PD detected algorithm have also compared with previous PRPDA or Neural Fuzzy algorithm, which has diagnose more conveniently by adding numerical values.

키워드