Effect of Platform Screen Door on fire in the subway station

스크린도어가 설치된 지하철 승강장의 화재유동 전산 수치 모사를 이용한 스크린도어의 화재 영향 연구

  • 장용준 (한국철도기술연구원, 환경화재연구팀) ;
  • 정우성 (한국철도기술연구원, 환경화재연구팀) ;
  • 박원희 (한국철도기술연구원, 환경화재연구팀) ;
  • 김학범 (한국철도기술연구원, 환경화재연구팀)
  • Published : 2007.11.08

Abstract

The present study is a basic investigation for systematically proceeding disaster prevention studying the effect of platform screen door in case of fire at the subway station. In the paper, the characteristics of screen door were surveyed and described. The fully closed platform screen door and the island type of subway station were employed for simulation-study. Numerical simulations of fire driven flow at the subway station with platform screen door were performed with commercial fire CFD code. For analyzing of the effect of platform screen door, the fire simulations with and without the platform screen door were compared. For the fire location, the one is located on the platform and the other case on the railway. The Ultrafast model was taken as fire growth scenario. The maximum heat release rate was 10MW. The propagated time of the heat and smoke to stairs was within 4 minute when the fire is located on the platform. However the heat and smoke propagation was block off by screen door when the fire is located on the railway.

본 연구는 플랫폼 스크린도어가 설치된 역사에서 화재시 스크린도어에 의한 효과와 화재에 대한 방재연구를 체계적으로 진행하기 위한 기초연구이다. 본문에는 스크린 도어의 종류와 특징에 대하여 기술하였다. 본 연구의 대상이 되는 스크린 도어에는 완전밀폐형이 설치된 역사를 대상으로 하였으며 승강장 종류는 섬식 승강장이다. 스크린 도어가 설치된 역사의 화재유동 전산수치모사에 화재전용 CFD code를 이용하여 수행하였다. 플랫폼 스크린도어의 영향을 분석하기 위하여 스크린도어가 설치된 경우와 설치되지 않은 경우를 해석 하였다. 또한 화원의 위치는 승강장과 선로부에 있는 경우로 나누었다. 화원의 성장시나리오는 Ultrafast model로 하였으며, 화원크기는 10MW로 하였다. 해석결과 플랫폼 스크린도어가 설치된 경우는 화원의 위치가 승강장에 있을 때 온도 및 연기의 전파가 주 탈출구인 계단에까지 4분 이내로 전파된다. 선로부에 있을 때는 스크린 도어에 의해 열, 연기 전파의 차단 효과가 있었다.

Keywords