Partial Discharge Quality Measurement improvement of XLPE Cable of 154kV by new method of FSA

박 센서 배열에 따른 154kV XLPE 케이블의 부분방전 검출 특성 연구

  • Published : 2006.11.09

Abstract

The system measuring the Partial discharge(PD) is very essential to investigate the hazard defects in the insulation systems of the high voltage engineering. We included two parts in this discussion; The proposed method of Foil Sensor Array and the normally used method m the practice. Firstly, it will be shown the improved sensitivity of our proposed FSA sensor compare with the existing normal foil sensor. And then, the linearity of detecting sensitivities of various kinds of FSA sensors such as $2{\times}2$, $2{\times}4$, $3{\times}3$ etc. using in our experiments, was shown. From the obtained results, we can see that FSA sensor is more sensitivity than normal foil sensor and the linear increment property of FSA sensitivities.

Keywords