3 Dimensional Numerical Simulation for the Closed Loop Heat Pump System Using TOUGH2

TOUGH2를 이용한 폐쇄형 지열펌프 시스템의 3차원 모델링 연구

  • 김성균 (서울대학교 지구환경과학부) ;
  • 배광옥 (서울대학교 지구환경과학부) ;
  • 이강근 (서울대학교 지구환경과학부)
  • Published : 2006.11.23

Abstract

To evaluate the effect of groundwater flow on the outlet temperature of a geothermal heat pump, 3 dimensional numerical simulations are performed considering both groundwater flow and pipe flow in the U-tube using TOUGHS, The present study involved the following 4 simulation cases (1) no groundwater flow, (2) slow groundwater flow (hydraulic conductivity: $1.0{\times}10^{-9}m/s)$, (3) fast groundwater flow (hydraulic conductivity, $1.0{\times}10^{-7}m/s$), and (4) groundwater flow varying with the depth (hydraulic conductivity: $1.0{\times}10^{-7}-1.0{\times}10^{-10}m/s$). The effect of groundwater flow on the outlet temperature is significant where hydraulic conductivity of aquifer is $1.0{\times}10^{-7}m/s$. Where hydraulic conductivity of aquifer is $1.0{\times}10^{-10}m/s$, however, that effect is negligible.

Keywords