Assessment of Fire-induced Damage to Tunnel Structural Members at Different Fire Scenarios

화재이력에 따른 터널구조물 시공재료의 화재손상 평가

  • 최순욱 (한국건설기술연구원 지반연구부) ;
  • 장수호 (한국건설기술연구원 지반연구부) ;
  • 권종욱 (나우이엔지(주)) ;
  • 배규진 (한국건설기술연구원 지반연구부)
  • Published : 2006.03.24

Abstract

In this study, a series of fire tests was carried out to evaluate fire-induced damage to structural members in tunnels. From the tests, the loss amount of concrete materials by the RWS fire scenario was slightly bigger than by the RABT fire scenario. Especially under the RWS fire scenario where the maximum temperature is over 1,200, the loss of concrete materials was mainly induced by melting. Generally, the loss of materials in reinforced concrete was slightly smaller than that in unreinforced concrete. Depending upon an applied fire scenario, fire-induced damage to shotcrete was quite different. From the real-time investigation of a specimen surface by a digital camcorder, it was proved that the material loss under the RABT fire scenario was mainly induced by spalling. However, it was also revealed that although fire-induced damage in the initial heating stage under the RWS was so close to that under the RABT, the material loss under the RWS at the later stage after 50 minutes elapsed since fire initiation was induced not by spalling but by melting.