Accident Risk Assessment between Power Cable Head and Safety Shutter in Medium Voltage Metal-Clad Switchgear

고압폐쇄분전반의 전력케이블 헤드와 안전셔터에서의 사고위험 평가

  • Shong, Kil-Mok (Electrical Safety Research Institute, subsidiary of Korea Electrical Safety Corporation) ;
  • Han, Woon-Ki (Electrical Safety Research Institute, subsidiary of Korea Electrical Safety Corporation) ;
  • Kim, Young-Seok (Electrical Safety Research Institute, subsidiary of Korea Electrical Safety Corporation)
  • Published : 2006.05.11

Abstract

This paper describes the accident analysis by modeling the current transformer mounting in meaium voltage metal-clad switchgear(MCSG). In analyzing the accident the reconstruction at the current transformer mounting(VCB connecting guide) has to be taken into account. The accident was modelled as a 3-phase ground fault mounting between the end plate of a high voltage lines and the safety shutter at the current transformer mounting of the VCB inside the metal clad switchgear. Since the outside maintenance of the metal clad switchgear is restricted by the enclosed compartments, its circumference has to be kept clean. Through the reconstruction results, it was confirmed that the fault of the enclosed switchboard could be reduced when the shutter made of Fe material was changed into an insulation.

Keywords