Comparison of the PMV and $CO_2$ concentration Characteristic in the Lecture Room with a Different Airflow rate of the Ventilation System and Heating System for heating season

강의실에서 환기시스템과 난방시스템의 풍량에 따른 PMV와 $CO_2$ 농도 특성 비교

  • Han, Chang-Woo (Graduate school of Mechanical and Information Engineering, University of Seoul) ;
  • Noh, Kwang-Chul (Graduate school of Mechanical and Information Engineering, University of Seoul) ;
  • Oh, Myung-Do (Department of Mechanical and Information Engineering, University of Seoul)
  • 한창우 (서울시립대학교 대학원 기계정보공학과) ;
  • 노광철 (서울시립대학교 대학원 기계정보공학과) ;
  • 오명도 (서울시립대학교 기계정보공학과)
  • Published : 2006.06.21

Abstract

In this paper, we performed the experimental and numerical study on the thermal comfort(TC) and indoor air quality(IAQ) in the lecture room with a different airflow rate of the ventilation system and heating system for heating season. Through the experimental results, we found out that there was considerably difference of the PMV but there was little difference of $CO_2$ concentration with a different heating system. From a numerical results, the best operating condition was that discharge airflow rate of SAC is 29 CMM and supply airflow rate of the ventilation system is 1,200 CMH from a viewpoint of TC and IAQ.