Eigenvalue Analysis of Power Systems with GTO Controlled SSSC by the RCF Method

GTO 제어 SSSC가 설치된 계통의 RCF 해석법에 의한 고유치 해석

  • Dong, Moo-Hwan (School of Electronic & Information Engineering, Kunsan National University) ;
  • Kim, Deok-Young (School of Electronic & Information Engineering, Kunsan National University)
  • 동무환 (군산대학교 전자정보공학부) ;
  • 김덕영 (군산대학교 전자정보공학부)
  • Published : 2006.07.12

Abstract

In this paper, the RCF(Resistive Companion Form) analysis method is used to analyze small signal stability of power systems including GTO controlled FACTS equipment such as SSSC. To apply the RCF analysis method in power system small signal stability problems, state transition equations of power system equipments and power systems with SSSC are presented. In eigenvalue analysis of power systems by the RCF analysis method, SSSC is modelled into the equivalents voltage source model and PWM switching circuit model. As a result of simulation, the RCF method is very powerful to calculate the oscillation modes exactly after the switching operations, and useful to analyze the small signal stability of power systems with periodic switching device such as SSSC.