Assessment of Insulation Condition for Generator Rotor Windings

발전기 회전자 권선의 건전성 평가

  • Published : 2006.07.12

Abstract

A shorted-turn test was performed at the Pyungtaek combined cycle power plant on gas turbine generators. The test was conducted using a permanent flux probe and on-line shorted-turn diagnosis system. The permanent flux probe installed in the generator air gap senses the field winding slot leakage flux and produces a voltage proportional to the rate of change signature unique to each field winding. We have also applied a voltage waveform analysis technique that can identify the pole location, slot number and number of shorted-turn with each slot.