Islanding detection of grid-connected photovoltaic inverters using Automatic phase-shift method
계통연계형 PV 인버터의 자동 위상 이동법에 의한 고립운전 검출
- Yun, Jung-Hyeok (Kyungpook National University) ;
- Kim, Heung-Geun (Kyungpook National University) ;
- Choi, Jong-Woo (Kyungpook National University) ;
- Chun, Tae-Won (Ulsan University) ;
- Lee, Hong-Hee (Ulsan University)
- Published : 2005.07.04
Abstract
Islanding of PV systems occurs when the uitilty grid is removed but local sources continue to operate and provide power to local loads. Islanding Is one of the serious problems in an electric power system connected with dispersed power sources. Also, this scan present safety hazards and the possibility of damage to other electric equipments. If the real and reactive power of RLC load and PV system are closely matched, islanding phenomena can't be detected by the passive methods. Several active methods were proposed to detect islanding phenomena. The most effective method is SFS method which was suggested by Sandia National Laboratory. In this paper, a new anti-islanding algorithm is proposed and its validity is verified through simulation and experimental results for utility interconnection of PV system.