Experimental Study on the Performance of an Air-Cooling System for Telecommunication Equipment

통신장비용 공냉형 냉각시스템의 성능 특성에 대한 실험적 연구

  • Jeon, Jong-Ug (Graduate School of Mechanical Engineering, Korea University) ;
  • Choi, Jong-Min (Department of Mechanical Engineering, Hanbat National University) ;
  • Heo, Jae-Hyeok (Graduate School of Mechanical Engineering, Korea University) ;
  • Kim, Yong-Chan (Department of Mechanical Engineering, Korea University)
  • 전종욱 (고려대학교 기계공학과 대학원) ;
  • 최종민 (한밭대학교 기계공학과) ;
  • 허재혁 (고려대학교 기계공학과 대학원) ;
  • 김용찬 (고려대학교 기계공학과)
  • Published : 2005.11.25

Abstract

The objective of this study is to analyze the cooling performance of an air- cooling system for telecommunication equipment. Temperature variation and capacity were measured in an actual unit for telecommunication equipment. In addition, the cooling performance was measured by installing a silicon rubber heater as a heat source in a cabinet. The standard thermal load for telecommunication equipment was approximately 293 W, and the maximum temperature of the heated surface was $64.5^{\circ}C$. The average and maximum temperatures of the heated surface were proportional to the inlet air temperature. When the heat load increased from 293 W to 400 W, the maximum temperature of the heated surface was higher than $64.5^{\circ}C$ even though the inlet air temperature decreased from 25 to $11^{\circ}C$.