A Study on the Application of Water Mist Fire Extinguishing System to Machinery Spaces

미분무수 소화설비의 선박용 기관실 적용에 관한 연구

  • 김기옥 (한국화재보험협회 방재시험연구원) ;
  • 안병호 (한국화재보험협회 방재시험연구원) ;
  • 양우진 (한국화재보험협회 방재시험연구원) ;
  • 김영한 (탱크테크(주))
  • Published : 2005.11.01

Abstract

A study to evaluate the fire extinguishing performance of the water mist system inside simulated machinery spaces according to IMO MSC/Circ.668 was performed. Fire tests were conducted inside a compartment having a area 100$m^2$(10m${\times}$10m) with a ceiling height of 10m and door opening of 2m${\times}$2m in size. Test fuels were used heptane, diesel, wood crib and mineral oil. Water mist nozzles were installed downward at ceiling and horizontally at bilge area. All fires in the test were extinguished within 15minutes of system activation and there was no reignition or fire spread.