Study on Evaporating Heat Transfer of HCs Refrigerants by Changing of Tube Diameter

관경별 탄화수소계 냉매의 증발 열전달에 관한 특성평가

  • 이광배 (부경대학교 냉동공조공학과) ;
  • 이호생 (부경대학교 냉동공조공학과) ;
  • 문춘군 (부경대학교 냉동공조공학과) ;
  • 김재돌 (동명대학 냉동공조과) ;
  • 윤정인 (부경대학교 기계공학부)
  • Published : 2005.11.01

Abstract

The experimental apparatus has been set-up as a conventional vapor compression type heat pump system. The test section is a horizontal double pipe heat exchanger. A tube diameter of 12.70 mm, 9.52 mm, 6.35 mm with 1.78 mm,1.52 mm,1.4 mm wall thickness each is used for this investigation. The local evaporating heat transfer coefficients of hydrocarbon refrigerants were superior to that of R-22. and the maximum increasing rate of heat transfer coefficient was found in R-1270. The average evaporating heat transfer coefficient increased with the increase of the mass velocity and it showed the higher values in hydrocarbon refrigerants than R-22. The highest evaporating heat transfer coefficient of all refrigerants was shown in a tube diameter of 6.35 mm with same mass flux.