Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference (한국조명전기설비학회:학술대회논문집)
- 2005.05a
- /
- Pages.349-354
- /
- 2005
An experimental research about the grounding resistance of the mesh electrode in the model of water tank
메쉬접지극의 접지저항에 관한 실증연구
- Kim, Ju-Chan (Kyungnam Univ.) ;
- Choi, Jong-Gyu (Masan college) ;
- Lee, Chung-Sik (Daewon Science College) ;
- Koh, Hee-Seog (Kyungnam Univ.)
- Published : 2005.05.13
Abstract
Recently, there are many equipment of electricity, electronics, and communication which need to grounding in the building. When the electric current flows into a certain grounding system in the same building, the potential rise of other grounding system is possible to be affected by its potential rise. This potential interference was affected by the surface potential, it is deeply related whit the electrode shape. In this paper, basic formula is deduced on the basis of both electrodes surface potential of grounding electrode in a source of the potential interference and groundidng electrode which receive the potential interference. Therefore the degree of potential interference as multiple groundidng electrode can be verified the simulated results by means of the simple model in advance. This is for investigating the grounding resistance of grounding electrodes, the experiment was performed with model-scale of the grounding system and the scaled model grounding system was to this experiment using a water tank of a stainless steel-hemisphere shape. since mesh electrodes have been widely in the general building, we're tried to analyze that this water tank model and it's simulation as well.
Keywords