Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 2005.11b
- /
- Pages.313-315
- /
- 2005
Fault location identification and protective coordination schemes presentation of distribution system interconnected Distributed Generation
분산전원이 연계된 배전계통의 사고지점 확인 및 보호협조 방안 제시
- Choi, Dong-Man (Chonnam National Univ.) ;
- Choi, Joon-Ho (Chonnam National Univ.) ;
- Ro, Kyoung-Soo (Dongguk Univ.) ;
- Moon, Seung-Il (Seoul National Univ.) ;
- Kim, Jae-Chul (Soongsil Univ.)
- Published : 2005.11.18
Abstract
Recently There has been growing interest in new renewable energy systems with high-energy efficiency due to the increasing energy consumption and environmental pollution problems. But an insertion of new distributed generation to existng power distribution systems can cause several problems such as voltage variations, harmonics, protective coordination, increasing fault current etc, because of reverse power. This paper was applied to fault location defecting a method as each Relay sensing fault current value and carried out short-circuit analysis by MATLAB and PSCAD/EMTDC programs and identity the faulted section o f22.9[kV] distribution system interconnected a large number of distributed generation. The existing protection system of 22.9[kV] power distribution system analyzed and the study on protective coordination recloser and Sectionalzer accomplished
Keywords