Review about test method for the full-insulation verification of circuit breaker rated on 800kV, 50kA
800kV, 50kA 차단기의 전절연 검증을 위한 시험방법 검토
- Park, Seung-Jae ;
- Suh, Yoon-Taek ;
- Yoon, Hack-Dong ;
- Kim, Yong-Sik ;
- Kim, Maeng-Hyun ;
- Koh, Heui-Seog
- Published : 2005.07.18
Abstract
In case of dead-tank circuit breaker with the earthed enclosure, the dielectric performance for phase to ground should be verified under the hot-gas condition produced by the current interruption. This test condition is required in breaking test duties with the rated short-circuit current and rated voltage. And, KERI has completed the reinforcement of the synthetic testing facilities and these facilities have the testing capacity which enables the full-pole testing for 800kV circuit breaker by adopting the series voltage injection method. So, this paper introduced the test circuit and procedures about the full-pole and the multi-part testing method which was devised to estimate the full -insulation of phase-to-ground for the multi-pole and dead-tank circuit breaker.