Analysis of Insulation Aging in Operating High Voltage Motors
운전중인 고압전동기에서 절연열화 분석
- Kim, Hee-Dong (Korea Electric Power Research Institute) ;
- Ju, Young-Ho (Korea Electric Power Research Institute)
- Published : 2005.07.18
Abstract
During normal machine operation, partial discharge(PD) measurements were performed with turbine generator analyzer(TGA) in five high voltage motors(rated 6.6kV). These high voltage motors were installed with 80pF capacitive couplers at the terminal box. The PD patterns were displayed two dimensional and three dimensional. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). Off-line PD measurements were conducted on five motors. These motors were energized to 3.81kV. The PD levels in pC were measured with a conventional digital PD detector. The comparison of positive to negative PD indicates whether the defect elements of PD are within the insulation or on the insulation surface. Internal discharges were generated in phase A, B and C of COP-B and pulv.-B, in phase B of Pulv. C and in phase C of Pulv.-D motor. Discharge at conductor surface was discovered in phase A of Pulv. D motor. Slot discharges occurred in three phases of Pulv. E motor.