A study on insulation characteristics with AC Breakdown Test for Stator Winding of 3.3kV class Induction Motor

절연파괴시험을 통한 3.3kV 유도전동기의 절연특성 연구

  • Published : 2005.07.18

Abstract

This test was performed to assess the corelation of insulation deterioration condition with breakdown voltage of the stator winding of 3.3kV class induction motors which have been in service for 10 years after being installed in 1993. The insulation diagnostic tests include resistance, polarization index(P.I), dissipation factor$({\Delta}tan{\delta})$, maximum partial discharges (Qmax) and AC breakdown test. we evaluated the corelation of insulation diagnostic test with AC breakdown test for stator wilding of high voltage induction motor.

Keywords