Analysis of Partial Discharge in High Voltage Motor Model Coils

고압전동기 모델 코일의 부분방전 분석

  • Published : 2005.07.18

Abstract

Five model coils of 6.6kV motor were manufactured with several defects. These stator coils have artificial defects such as void of groundwall insulation, removal of semi-conductive coating and damage of strand insulation. Epoxy-mica coupler(80 pF) was connected to five model coil terminals, respectively The voltage applied to the coils was 3.81kV, 4.76kV, 6.0kV and 6.6kV. Partial discharge(PD) tests performed in the laboratory and shield room. Digital PD detector (PDD) and turbine generator analyzer(TGA) were used to measure PD activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in pC were measured with PDD. PD patterns of model coils were indicated the internal and slot discharges. PD patterns coincide with both PDD and TGA.