Resistive leakage current following arresters is an important indicator of ageing, but total leakage current and its harmonic analysis are widely used in diagnosing arrester soundness because of difficulties in measuring resistive leakage current. In this paper, we proposed a new method for measuring resistive leakage current, which is quite different from the conventional methods such as a self-cancel method and a synchronous rectification method. The proposed method is based on that the magnitudes of resistive leakage currents are equal at the same voltage level. To confirm the possibility of the proposed method. we fabricated a leakage current measurement device and designed an analysis program that can analyze resistive leakage current. Comparing with other methods. this technique does not need a complex circuitry and is very simple to complete.