Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference (한국전기전자재료학회:학술대회논문집)
- 2004.05b
- /
- Pages.65-68
- /
- 2004
A Leakage Current Analysis of EHV Porcelain Insulators by Artificial Contamination Method
초고압 송전용 자기애자의 인공오손법을 통한 누설전류 분석
- Choi, In-Hyuk (KEPRI) ;
- Choi, Jang-Hyun (KEPRI) ;
- Jung, Yoon-Hwan (KEPRI) ;
- Lee, Dong-Il (KEPRI)
- Published : 2004.05.21
Abstract
This paper researched leakage current characteristics of artificially contaminated EHV insulators through construction of long-term testing facility. Insulators were contaminated and classified into the ESDD contaminated levels under IEC standards method. As the test results of contaminated insulators was carried out several experiments, leakage current greatly increased during initial rainfall. After contaminated insulators were naturally washed by rain, leakage current was not increased.