Characteristics Leakage Current of Surface Discharge according to Kaolin Contamination by Deteriorated Polymer Insulators

열화된 고분자애자의 카올린 오손에따른 표면방전특성

  • Published : 2004.07.05

Abstract

The paper presents the results of using the fundamental and the low frequency harmonic components of leakage current to study aging of EPDM insulator for contaminated condition by kaolin. The largeer the leakage current during 200ms, the higher harmonic component at 60hz. The harmonic component at 60hz and the odd order harmonics is increase relation without Kaolin Conent. Arcing on the surface was always associated with distortion in the leakage current; hence the low frequency components of the leakage currnent can be used as a means to evaluate the surface degration. Both the fundamental and 3rd & 5th harmonics increase dry-band activity.

Keywords