Ground impedance of deeply driven rod in high frequency domain
고주파수 영역에서 심매설 접지전극의 접지임피던스
- Published : 2004.11.03
Abstract
A ground resistance is a good index of performance in a grounding system, but it does not reflect the performance in transient states. Recently long vertical ground rods in urban areas are often installed. But because of the inductance of long ground rods the ground impedance at high frequency might be greater than its resistance at low frequency. In this paper, a ground impedance of deeply driven ground rod has been measured in the frequency range from 10 kHz to 50 MHz. As a result, the ground impedances of a deeply driven ground rods are almost constant at the frequency range less than 100 kHz. However at high frequency the ground impedance showed the strong frequency dependance.