한국조명전기설비학회:학술대회논문집 (Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference)
- 한국조명전기설비학회 2004년도 춘계학술대회 논문집
- /
- Pages.502-505
- /
- 2004
완화전류 측정에 의한 지중배전케이블의 열화진단
Aging Diagnosis of Underground Distribution Power Cables by Isothermal Relaxation Current Measurement Equipment
- 발행 : 2004.05.07
초록
The purpose of this experiment is to modify diagnosis criterion of isothermal relaxation current(IRC) measurement equipment which is using for distribution cable diagnosis. We're using this system for several years in the field instead of DC leakage current measurement and lots of cables were replaced. But we have to investigate on the reliability of this equipment for our cables because we didn't carried out condition assessment of extracted cables after field diagnosis by this equipment. It is important thing for cable maintenance. If the replacement criterion is improper we can not prevent failures or will waste budget on account of replacement of the sound cables. In this papar we selected field installed cables and injected silicone fluid to the cables for insulation rehabilitation. In order to prove reliability of the diagnosis equipment we compared diagnosis results and AC breakdown strength according to operating time after silicone treatment. This is the results of the field test for 1 year.
키워드