Current Status of the Feeder Demand Factor in Small Size Apartments

중소형 아파트에서의 전력간선 부하 실태

  • 이기홍 (대한주택공사 주택도시연구원)
  • Published : 2004.05.07

Abstract

This paper gives a measurement data of the feeder demand factor in small size apartments. The power load measurement data of the feeder shows that the feeders have $10{\sim}30[%]$ margin in capacity. But this margin is not enough to keep up with the trend of power consumption increase from long term standpoint. So it is necessary to measure the feeder power load periodically for the purpose of optimal feeder capacity estimation

Keywords