한국소음진동공학회:학술대회논문집 (Proceedings of the Korean Society for Noise and Vibration Engineering Conference)
- 한국소음진동공학회 2004년도 춘계학술대회논문집
- /
- Pages.985-990
- /
- 2004
- /
- 1598-2548(pISSN)
배관-유체 연성진동을 이용한 누수지점 탐지알고리듬 개발연구
An Algorithm for Leak Locating using Coupled Vibration of Pipe-Water
초록
Leak noise is a good source to identify the exact location of a leak point of underground water pipelines. Water leak generates broadband noise from a leak location and can be propagated to both directions of water pipes. This sound propagation due to leak in water pipelines is not a non-dispersive wave any more because of the surrounding pipes and soil. However, the necessity of long-range detection of this leak location makes to identify low-frequency acoustic waves rather than high frequency ones. Acoustic wave propagation coupled with surrounding boundaries including cast iron pipes is theoretically analyzed and the wave velocity was confirmed with experiment. The leak locations were identified both by the acoustic emission (AE) method and the cross-correlation method. In a short-range distance, both the AE method and cross-correlation method are effective to detect leak position. However, the detection for a long-range distance required a lower frequency range accelerometers only because higher frequency waves were attenuated very quickly with the increase of propagation paths. Two algorithms for the cross-correlation function were suggested, and a long-range detection has been achieved at real underground water pipelines longer than 300m.
키워드