Improvement of the Exponential Experiment System for the Automatical and Accurate Measurement of the Exponential Decay constant

지수감쇠계수의 자동 및 정밀 측정을 위한 지수실험장치 개선

  • Published : 2004.06.01

Abstract

The previous exponential experiment system has been improved for the automatical and accurate axial movement of the neutron source and detector with attaching the automatical control system which consists of a Programmable Logical Controller(PLC) and a stepping motor set. The automatic control program which controls MCA and PLC consistently has been also developed on the basis of GENIE 2000 Library. The exponential experiments have been carried out for Kori 1 unit spent fuel assemblies, Cl4, Jl4 and G23, and Kori 2 unit spent fuel assembly, J44, using the improved systematical measurement system. As the results, the average exponential decay constants for 4 assemblies are determined to be 0.1302, 0.1267, 0.1247, and 0.1210, respectively, with the application of Poisson regression.

기존의 지수실험장치에 PLC와 스텝핑 모터로 구성된 자동화 제어장치를 부착하여 중성자 선원과 검출기를 자동으로 정확하게 이동할 수 있도록 개선하였다. 또한 GENIE 2000 라이브러리에 기반을 둔 MCA와 PLC를 동시에 구동할 수 있는 통합자동화 프로그램을 개발하였다. 이와 같이 체계적인 장치로 개선된 실험장치를 사용하여 고리 1 호기의 사용후핵연료 집합체, Cl4, Jl4 및 G23과 고리 2 호기의 사용후핵연료 집하체, J44의 대한 지수실험을 수행하였다. 그 결과 4 개 집합체에 대한 평균 지수감쇠계수는 각각 0.1302, 0.1267, 0.1247 및 0.1210으로 결정되었다.

Keywords