Proceedings of the KSR Conference (한국철도학회:학술대회논문집)
- 2004.06a
- /
- Pages.1422-1424
- /
- 2004
Diagnostic Technique and Device for Railway Arresters
철도용 피뢰기 진단기술 및 장치
- Published : 2004.06.01
Abstract
Various deterioration diagnostic techniques and devices are suggested, and most of which measure leakage current components as an indicator of arrester ageing. However, the techniques based on the magnitude of leakage current measure simply RMS or peak value of leakage current components and do not provide detailed information needed in the diagnosis. In this study, we found that the phase vs. wave height of total leakage current is changed or a new wave height is produced with arrester ageing. To complete the new technique, we designed an arrester diagnostic device which is composed of a current detection circuit, an optical transmission circuit, and an analysis program. After measurement of the total leakage current, magnitudes, phase vs. wave height, and harmonics of the leakage current components are analyzed by the microprocessor based device. From the experimental results, we confirmed that the device can measure most parameters needed for the arrester diagnostics and analyze an initial deterioration state.
Keywords