Selection Criteria for the Traction Power Supply Line of the Light Rail Transit System

경량전철 전차선 용량 선정방법

  • 정상기 (한국철도기술연구원 경량전철연구팀) ;
  • 정락교 (한국철도기술연구원 경량전철연구팀) ;
  • 조홍식 (한국철도기술연구원 경량전철연구팀) ;
  • 한석윤 (한국철도기술연구원 경량전철연구팀) ;
  • 이안호 (한국철도기술연구원 경량전철연구팀) ;
  • 백병산 (현대중공업 기전연구소)
  • Published : 2003.05.01

Abstract

In this study we examined the method to select the size of the conductor rail for light rail system. Study results shows that using the conductor rail with lower resistivity requires fewer power substation, which results in lower construction cost. It also produces less copper loss. Therefore first choose the conductor rail with lowest resistivity and select the substation location, Next conduct computer simulation study to confirm it meets voltage requirement. if the minimum voltage is well above the required minimum voltage, substation number can probably be further reduced.

Keywords