Investigation for Earth Resistance and Leakage Current of D/L

배전선로 접지저항 및 누설전류 실태조사

  • 이현구 (한국전기연구원 지중시스템연구그룹) ;
  • 하태현 (한국전기연구원 지중시스템연구그룹) ;
  • 배정효 (한국전기연구원 지중시스템연구그룹) ;
  • 하윤철 (한국전기연구원 지중시스템연구그룹) ;
  • 김대경 (한국전기연구원 지중시스템연구그룹)
  • Published : 2003.11.13

Abstract

The sharing of common corridors by electric power transmission lines and pipelines is becoming more common place. However, such corridor sharing can result in undesired coupling of electromagnetic energy from the power lines to the near facilities. This causes induced voltages on underground metallic pipelines due to the power line currents. This could cause AC corrosion in the pipeline, which could in turn lead to disastrous accidents, such as gas explosion or oil leakage. This paper investigates for the limitation of induced voltage on the buried metal structures which is used in the inside and outside of the country. And then we measure the earth resistance and leakage current of 22.9kV distribution lines and pipe to soil potential of near pipelines in Seoul Korea. Hereby we can see the leakage current flowing through the earthing electrode have an effect on near pipelines.