The characteristic of leakage current of ZnO block varistor according to fault conditions of three-phase four-wire distribution system

3상 배전계통의 고장조건에 따른 산화아연 피뢰기 소자의 누설전류 특성

  • 이복희 (인하대 차세대 고전압전력기술연구센터) ;
  • 최휘성 (인하대 차세대 고전압전력기술연구센터) ;
  • 강성만 (인하대 차세대 고전압전력기술연구센터) ;
  • 박건영 (인하대 차세대 고전압전력기술연구센터) ;
  • 이수봉 (인하대 차세대 고전압전력기술연구센터) ;
  • 오성균 (인하대 차세대 고전압전력기술연구센터)
  • Published : 2003.11.13

Abstract

Kinds of most frequent faults happened on overhead distribution system are the single line-to-ground fault, the line-to-line fault and the two line-to-ground fault. Occasionally, the three line-to-ground fault and the disconnection of a wire are happened in severe conditions. In this study, the single line-to-ground fault, the line-to-line fault, two line-to-ground fault on three-phase four-wire overhead distribution system were experimentally simulated and characteristics of total leakage current of distribution arrester caused by these faults were investigated. Also, the changing aspect of total leakage current of distribution arrester caused by voltage variation was investigated. In a consequence, abnormal voltages caused by voltage variation, the line-to-line fault, the two line-to-ground fault have a little effect on total leakage current of ZnO arrester. But abnormal voltages caused by the single line-to-ground fault have an important effect on total leakage current of ZnO arrester.