Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 2003.04a
- /
- Pages.208-211
- /
- 2003
Wireless parallel operation of high voltage DC power supply using steady-state estimation
정상상태 판별을 이용한 고전압 직류전원장천의 Wireless 병렬 운전
- Son, H.S. (Korea Electrotechnology Research Institute) ;
- Baek, J.W. (Korea Electrotechnology Research Institute) ;
- Yoo, D.W. (Korea Electrotechnology Research Institute) ;
- Kim, J.M. (Pusan National Univ.) ;
- Kim, H.G. (Kyungpook National Univ)
- Published : 2003.04.24
Abstract
This paper presents an improved droop method of the high voltage DC power supply which minimizes the voltage droop of a parallel-connected power supply. Conventionally, the droop method has been used to achieve a simple structure and no-interconnections among the power sources. However, it has a trade-off between output voltage regulation and load sharing accuracy. In this paper, the droop is minimized with a current and droop gain control using steady-stage estimation. The proposed method can achieve both high performance voltage regulation and load sharing. Two 10kV, 100mA parallel power modules were made and tested to verify the proposed current-sharing method.
Keywords