HCM기반 뉴로-교지 시스템을 이용한 변압기 보호 알고리즘

Protecive Algorithm for Transformer Using Nuro-Fuzzy System based on HCM

  • 발행 : 2003.07.21

초록

The second harmonic component is commonly used for blocking differential relay in power transformers. However, it is difficult to distinguish between inrush and internal winding fault with differential current protective relaying. This paper proposed a new method using Nuro-Fuzzy System based on HCM(Hard C-Means). The proposed system is more objective and systematic than existing model. The data used in input are 3-phase primary voltage and fundamental harmonic of differential current. Various states of transformer are simulated using BCTRAN and HYSDAT of EMTP. As a result of the application of algorithm in various cases, the exact discrimination between internal winding fault and inrush is performed.

키워드