Measurement of a temperature and components of arc plasma with a spectroscopic method

분광법을 이용한 아크 플라즈마의 온도 및 성분 측정

  • Jeong, Young-Woo (LG Industrial Systems, Electrotechnology R&D Center) ;
  • Lee, Sang-Youb (LG Industrial Systems, Electrotechnology R&D Center) ;
  • Park, Hong-Tae (LG Industrial Systems, Electrotechnology R&D Center) ;
  • Oh, Il-Sung (LG Industrial Systems, Electrotechnology R&D Center)
  • Published : 2003.07.21

Abstract

This paper describes an experiment of detecting a temperature and components of arc plasma of electrical circuit breaker with a spectroscopic system. The system includes an optical fiber, a monochromator which has three gratings from low to high resolution and ICCD of which time resolution is 50 ns. This system enables measuring a temperature and components of arc plasma of a circuit breaker which is generated and extinguished in a few ms. We use a Planck's law and Boltzmann Plot method for calculating a temperature of arc plasma. A Xenon lamp is used for calibrating the system and this is very important for calculating a temperature of arc plasma. In this study, Arc plasma of Ag and Cu contact was investigated and these represent the contact of low voltage and extra-ultra high voltage circuit breaker, respectively. 8 $kA_{rms}$ test current was applied with a capacitor bank.

Keywords